Mains Earthing Systems
The Earth is an integral part of our power system. It can be used to
improve electrical safety, reduce energy losses or save on the cost
of a dedicated conductor. Here, we look at the different Earthing
systems used worldwide and how they work.
By Brandon Speedie
T
he Earth’s crust is moderately conductive thanks mainly to the salts
of sodium dissolved in water and, to
a lesser extent, elements such as calcium, potassium, and magnesium.
These charge carriers can move freely
through soil and rock as long as they
remain dissolved in water. The result
is a surprisingly conductive electrolyte – see Fig.1.
There are two broad reasons for using
the Earth as a conductor.
As a functional conductor
The most obvious use of the Earth is
to save on the cost of a dedicated conductor. One example is the Single Wire
Earth Return (SWER) line, a common
way to distribute power in rural areas.
0.01
0.1
1
In this case, a significant cost saving
can be achieved by only having a single
overhead conductor on a power line
(see Figs.2 & 3).
The return current (for Neutral)
flows through the soil back to the substation or generator. This can sometimes be a distance of hundreds of
kilometres/miles.
The Earth is also commonly used
in RF applications. A monopole antenna relies on a ground plane to radiate and receive effectively, a role
very commonly allocated to ‘terra
firma’ (Latin for “firm land” or perhaps “solid ground”).
Another application of Earth is on
grid-scale solar farms. Solar panels
are effectively three-terminal devices;
Resistivity (Ωm)
10
100
1000
10,000
igneous and
metamorphic rocks
graphite
mafic
felsic) mottled duricrust
zone
saprolite
Safety
Perhaps the most prominent function
of Earth is to provide electrical safety.
100,000
massive sulfides
(igneous rocks:
they have a positive output, a negative
output and a frame or chassis.
If the frame is left electrically unconnected, it can float to a different
voltage from its other two terminals.
Charge carriers will then begin to migrate out of the substrate in a process
known as Potential Induced Degradation (PID). This leads to reduced yield
and eventually, early failure.
On commercial solar farms, care is
taken to ensure the panel mounting solution is well bonded to Earth and that
the array DC voltage does not float too
far from the Earth’s potential.
shield
unweathered rocks
weathered layered
(metamorphic rocks)
clays
gravel and sand
glacial sediments
tills
shales
sandstone and conglomerate
sedimentary rocks
dolomite, limestone
lignite, coal
salt water
permafrost
fresh water
water, aquifers
sea ice
100,000
10,000
1000
100
10
1
0.1
0.01
Conductivity (mS/m)
Fig.1: resistivity figures for some common components of the Earth’s crust. Note
the different units on the top and bottom horizontal axes, which are inversely
equivalent; as S (siemens) is the inverse of W (ohms), 1mS is equivalent to 1kW.
Source: GeoSci Developers – https://pemag.au/link/abu7 (CCA 4.0).
44
Fig.2: SWER line in South Australia.
The unusual pole construction is
concrete sandwiched between two
steel beams, known as a “Stobie pole”.
Practical Electronics | July | 2026
Mains Earthing Systems
In normal operation of a single-phase
AC circuit, current flows into or out of
the Line conductor, through the load,
and returns via the Neutral conductor.
In a fault scenario, an Earth connection
gives a low impedance path for current to flow, which will usually trip a
circuit breaker.
In some scenarios, the fault will not
draw enough current to trip the circuit breaker, but it should be enough
to trigger a Residual Current Device
(RCD).
In an RCD, the Line and Neutral conductors both pass through a current
transformer (CT). In the absence of a
fault, the current flow is balanced between Line and Neutral, so the magnetic
fields of these two currents cancel, and
no net current is detected – see Fig.4.
In a fault scenario, current flows
through Line, but not all is returned
via the Neutral; some flows through
the Earth connection.
This imbalance is detected in the
RCD, which will typically trip once
the imbalance exceeds 30mA (although
more sensitive RCDs exist, eg, 15mA;
the trip current is a balance between
sensitivity and nuisance tripping).
The Earth can also be used to ensure
electrical safety during the normal
operation of a grid. The most prominent such application is lightning sup-
pression. If the potential difference
between the Earth’s surface and the
power lines were left uncontrolled,
a direct strike from a lightning bolt
would charge up the network to a
high voltage, leading to arc-over at
the insulators.
It is therefore critical that this energy
is shunted to Earth to maintain grid tolerances. Earth is also a logical place to
shunt this charge as the lightning originates from a static buildup between
the ground and the atmosphere.
Types of Earthing systems
Earthing schemes used in a mains
grid are commonly described by a sequence of letters based on where the
circuit Earth originates from.
“T” (terra; Latin for “Earth”) refers
to a direct connection to the soil of
the Earth. This is typically achieved
by driving a conductive stake into the
ground, or perhaps multiple stakes
and/or bonding to buried metal pipes.
In larger installations, such as substations or generators, a dedicated buried
circuit or ‘Earthing ring’ made of bare
wire (usually copper) encircles the
installation.
“I” (insulatum; Latin for “insulated”) means no connection to Earth or
a high-impedance connection through
an Earthing resistor.
“N” (network) means the Earth connection is via the network or grid.
Network Earths will still connect to
the soil at some point, but this may
be some distance away, not at a local
Earth stake, as with terra (T).
RCD
CT
LINE
NEUTRAL BUSBAR
NEUTRAL
LOAD
MEN
LINK
EARTH
BUSBAR
Fig.4: a Residual Current Device
(RCD). Usually, current flows to or
from the Line conductor through the
load and is returned via Neutral. The
magnetic fields of the two conductors
are cancelled, so the CT detects no net
current. A small amount of leakage
between Line and Earth, shown as a
thin red line here, is enough to trip
the RCD.
“C” (combined) means the circuit
Neutral and Earth are combined into a
single conductor in the network.
“S” (separate) is where the circuit
Neutral and Earth are run as separate
conductors in the network.
The Earthing system can thus be
described by two letters, the first indicating the source Earth, and the other
the load Earth.
TT (Terra-Terra)
Terra-terra networks are physically
connected to Earth at both the generator and load (see Fig.5). Typically,
this will be at the low-voltage distribution transformer and the customer’s
premises.
TT networks rely heavily on the
Earth connection’s integrity, so care
is taken to ensure a sufficiently low
Earth loop impedance. This can include
tight specifications around Earth stake
Terminology
Fig.3: the start of the SWER line shown
in Fig.2. The three conductors on the
right are 33kV phase-to-phase, or
19kV from phase to Neutral/Earth. The
SWER line taps off the middle phase
and extends to the left. The return
Neutral current flows via Earth.
Practical Electronics | July | 2026
Phrases such as Earth, Neutral, common and ground are sometimes used
somewhat interchangeably. They can be confusing terms, particularly from our
perspective as electronics enthusiasts.
Earth: a connection to terra firma, either directly through an Earthing stake,
or via a conductor that is bonded at some point with Earth.
Neutral: the return current of a single-phase AC supply. Typically, this will be the
centre point of a star-connected three-phase circuit. In regular operation, most
networks should have very little voltage difference between the Neutral and Earth.
Ground: a common node in a circuit, usually at 0V DC potential. Confusingly,
ground can be ‘grounded’ by tying to ‘Earth’, but it is uncommon in modern usage.
Floating circuits are generally considered to have a ‘ground’, but it could drift
relative to Earth; it is usually the negative end of a battery or similar and is used
as a local reference and/or current return. In a circuit running directly from the
mains, ‘ground’ may even be connected to (or very close to) the Line potential!
Some circuits can have multiple grounds (analog, digital etc).
Common: a node in a circuit shared by many components. It is sometimes used
interchangeably with ‘ground’ but can also be used where multiple signals are
tied together. Examples are a common bus in a multiplexed display or a common
signal tying multiple opto-isolators together.
45
Educational Feature
construction and placement, as well
as considerations of soil conductivity.
This is particularly important in cold
areas, where frozen soil dramatically
increases resistivity, or in high rainfall
regions, where soil electrolytes are diluted, leaving few charge carriers for
conduction.
Even given these additional requirements, a standard overcurrent breaker
is not guaranteed to trip from an Earth
fault. As a result, TT customers will
almost always need Earth leakage protection in the form of an RCD.
Historically, TT networks were not
popular due to the difficulty of ensuring safety without Earth leakage
protection. The advent of cheap RCD
breakers has led to its increasing use
worldwide, such that it is now the
most common scheme.
Many parts of Europe, including
France, Denmark, Belgium, Spain,
Italy, and Portugal, are now predominantly TT, as well as Japan, Malaysia,
Argentina and many others. Germany
extensively uses TT outside of metropolitan areas.
IT (Insula-Terra)
Insula-terra networks are connected
to Earth at the customer’s end but not
at the generator or distribution transformer (Fig.6). Therefore, the Line and
Neutral connections have no reference
to Earth, which minimises shock hazards. The reader may recognise this
advantage from using an isolation
transformer when working on mainspowered electronics.
IT networks are often referred to as
“first fault free”, as any fault will convert the system into another scheme
(usually TN) while the fault is present,
and subsequent faults may be dangerous. This is why IT networks are not
common worldwide, except in specialised applications.
This includes hospitals, where patients are at a higher risk of shock
when coupled to medical equipment,
and industrial areas where a flammable atmosphere may be present, so the
risk of sparking needs to be minimised.
Fig.5: the TT Earthing scheme.
46
Scandinavia is an exception, where
frozen ground and rocky geology make
Earthing difficult. Norway in particular makes heavy use of IT Earthing.
In India, a variation of the IT network called Resistance Earthed Neutral (REN) is used in mining areas. A
Neutral grounding resistor limits the
Earth current to 750mA.
TN-C (Terra-Network-Combined)
Terra-network-combined systems get
their Earth from the network by combining it with the Neutral conductor
(Fig.7). This combined conductor is
commonly referred to as the Protective Earth Neutral (PEN).
In a TN-C network, the distribution
transformer is Earthed at the source
end, which is also connected to the
circuit Neutral. This PEN conductor
then runs along the poles and wires of
the grid to customer premises, where
it is used as the “Earth”.
TN-C networks do not require an
Earth stake at the customer premises
or RCD breakers as in a TT or IT network, but they are extremely reliant
on the integrity of the PEN. If there is
a break in this conductor, the customer load will act like a pullup resistor,
raising the potential of Neutral/Earth
to mains voltage; a hazardous situation (see Fig.11).
TN-C networks also suffer from conducted interference. As the circuit
Neutral is combined with the Earth,
coupled noise from heavy industrial
equipment can pass through the network and cause problems with sensitive equipment such as telecommunications broadcast infrastructure.
Fig.11: a Neutral fault with the
TN-C scheme. The customer load
acts like a pullup resistor, raising
the Earth to a high voltage and
creating a shock hazard.
conductor. TN-S is used extensively
in India.
TN-C-S (Terra-Network-Combined-Separate)
Terra-network-combined-separate
networks are a hybrid of the TN-C and
TN-S systems. The source transformer is Earthed, while a combined PEN
conductor emanates onto the network
(Fig.9). The PEN is split into dedicated
Neutral and Earth conductors at some
agreed location (usually the customer’s
switchboard).
TN-C-S is widely used in the UK,
USA, Canada, Israel, Australia and
New Zealand – see Fig.14. Germany
also predominantly uses TN-C-S in
metropolitan areas.
MEN (Multiple-Earthed-Neutral)
Terra-network-separate networks
run a dedicated Earth on the network,
separate from the Neutral conductor
(Fig.8). The distribution transformer
is Earthed at the source end and connected to two conductors. One is the
Neutral, while the other is a dedicated Earth – see Fig.13. TN-S networks
are the safest configuration but are
also more expensive, given the added
Australia and New Zealand use the
Multiple Earthed Neutral (MEN system)
– see Fig.10. It is a TN-C-S system,
though TT may be permitted in some
situations – usually rural areas. Unusually for TN-C-S, an Earth stake is
mandatory at each customer premises.
In MEN networks, the source distribution transformer is Earthed, and a
combined PEN conductor runs in the
grid. The PEN is Earthed at multiple
points throughout the network, including at the customer stake.
This gives good immunity against
a broken Neutral; if the customer is
downstream of the fault, their PEN
will not rise to a dangerous potential
thanks to the Earth stake at their premises and any neighbouring premises or
network Earths.
Fig.6: the IT Earthing scheme.
Fig.7: the TN-C Earthing Scheme.
TN-S (Terra-Network-Separate)
Practical Electronics | July | 2026
Mains Earthing Systems
Fig.12: this configuration stops
the communications cable shield
from drifting too far from Earth. It
keeps it at a low AC impedance via
the capacitor but will not form an
‘Earth loop’.
At the customer premises, the combined PEN connects to the Neutral bar
in their switchboard. This busbar then
distributes the Neutrals to all of the
circuits within the installation. Separately, a dedicated Earthing busbar
connects to the “Earth” conductor
emanating throughout the property,
as well as the Earth stake.
The Earth busbar and the Neutral
busbar are joined by a single strap,
known as the “MEN link”. This link
is the separation point between the
TN-C scheme on the network and the
TN-S scheme within the customer
premises.
Earth integrity
The Earth connection is convenient,
as it can be assumed to be the same
voltage across multiple installations,
even if they are geographically separated. But as the soil has a finite resistance, this is not always true.
This can create problems where two
circuits are bonded to mains Earth and
are also linked by conductors, similar
to a local ‘ground loop’ or ‘earth loop’
that can cause problems with audio
electronics.
This is particularly problematic when
large conductive structures are located
near high-power switching gear. This
might be a steel fence around a switchyard or a buried gas pipeline adjacent
to power lines. In a fault, a large current
might flow into ‘Earth’, raising the local
voltage near the Earthing stake/ring. If
the metal structure is close enough to
this fault, its voltage will rise.
Fig.8: the TN-S Earthing scheme.
Practical Electronics | July | 2026
If someone touches this structure,
they may receive a lethal voltage despite being far from the actual fault.
This is because the metal is a better
conductor than the Earth, so the ground
they are standing on is at a different
voltage than the ground near the fault.
This is known as a ‘touch potential’
and is a major hazard in high-power
assets.
Editor’s Note: in extreme cases, there
can be enough potential between workers’ feet to electrocute them. Electrical
workers are trained to hop if they suspect such a fault exists!
Similarly, industrial Ethernet networks can also suffer from ground
loops and unequal Earthing. Ethernet
uses differential signalling, so it is
commonly run over UTP (Unshielded
Twisted Pair) cabling. A high Common
Mode Rejection Ratio (CMRR) amplifier cancels any coupled noise or
interference at the receiver. Thus,
shielded cable is not needed for noise
immunity.
Despite this, shielded or foiled Cat6
cabling is common in industrial settings. Often, the designer will reason
that shielded cable will be better than
unshielded, so it is worth the marginal
cost increase. However, it can often be
more trouble than it is worth.
Ethernet uses “magnetics” (signal
transformers) at the receiver and transmitter to galvanically isolate the channel, preventing ground loops from forming. Shielded cable effectively breaks
this isolation by connecting a conductor directly between the receiver and
transmitter.
If there is any Earth imbalance between this equipment, large currents
can flow, which can cause interference
or damage. For this reason, if shielded
Ethernet cable is used, it is often only
Earthed at one end of the cable, or
better still, connected through a parallel RC combination, perhaps 1MW ||
100nF (see Fig.12).
The resistor weakly holds the shield
at a known voltage, while the capacitor offers a low impedance path for AC
PE
voltages (coupled interference).
Fig.9: the TN-C-S Earthing scheme.
Fig.13: the TN-S scheme in Namibia.
The five conductors (from bottom to
top) are Earth, Neutral & three Line
phases. Note how the Earth wire has a
smaller diameter than the others.
Fig.14: the TN-C-S scheme in
Melbourne, Australia. The
distribution transformer feeds the four
horizontal conductors directly above
it. The second conductor from the left
is the combined Neutral/Earth (PEN),
while the other three conductors are
the Line phases, 400V Line-to-Line or
230V Line-to-Neutral. An Earth stake
(out of shot) connects to the conductor
running up the left of the pole,
partially covered by a white conduit.
The transformer is fed on the primary
side by the three conductors at the top
with 22kV between phases.
Fig.10: the MEN Earthing scheme.
47
|